Infrared Thermal Imaging Inspection Miami Dade Thermography Electrical, Thermographer Level II Certified Broward Boca Raton Insurance Test 30/40 Year Recertification Building Report Cost

How much does a Miami Dade inspection for 40 Year Recertification cost

Cost starting at $800. Removal of covers is usually $100 fixed, plus $10 per piece of equipment or device.

List of Equipment to be inspected should be provided by the Engineer signing and sealing the Report.

One of our Consultant Licensed Electrical Engineers will sign and seal our Building Recertification Inspection Reports

We are not responsible for submission.

305-606-4732

Thermographer Level II.

Choose the right Thermographer: licensed in an ELECTRICAL field.

The Miami Thermal Imaging inspection of electrical equipment shall be performed by a Certified Thermographer (Level II, III) who is qualified and trained to recognize and document thermal anomalies in electrical systems and possesses over 7 years of experience inspecting electrical systems associated with commercial buildings.

Level II Thermographers - Seven (7) Years of experience can be only justified by holding a license in an electrical field as a Professional Electrical Engineer, an electrical contractor, or an electrical building inspector. Cities are rejecting thermographers not holding an electrical license and other licensees in non-electrical fields.

Level II and III Certified Thermographer, Consultant Licensed Engineers working with us, Home Camera Scan Testing Report for systems operating at 400 Amperes or greater, Commercial, Residential Insurance. When required, Thermographic Re Inspection is only for Thermal issues.

Many times it is needed to perform an Equipment Survey for Infrared Electrical Inspection. The survey will identify all required equipment that needs to be inspected to follow the guidelines for 40 Year Recertification, as per County Board of Rules and Appeals (BORA).

This survey needs to be approved or provided by your engineer or records.

Our Thermographer Reinspection, when required, will be only for thermal problems detected. Other Electrical issues found by the Engineer are not inspected by us.

Please, be sure your service is more than 400 amps, before ordering the survey.

Thermal Imaging Electrical Infrared Inspection 10 Year Recertification.

Electrical Infrared Thermography Inspection Miami Dade, Home Thermal Imaging Testing, Certified Thermographer Level II. New requirement for Building Inspection 30/40 Year Recertification Cost Miami Dade County.

Level II and III Certified Infrared Thermography Electrical Home Inspection Services 40 Year Building Recertification Hialeah, Coral Gables, Homestead, Kendall West, Kendale Lakes, The Hammocks, Aventura, Bal Harbour, Bay Harbor Islands, Key Byscayne, Biscayne Park, Cutler Bay, Doral, El Portal, South Florida City, Golden Beach, Indian Creek, Medley, North Bay Village, Opa-Locka, Palmetto Bay, Pinecrest, Doral, Condo South Florida, Opa-Locka, Sweetwater, Fort Lauderdale, North Hollywood, Dania, Pompano, Hallandale, Pembroke Pines, Miramar, Weston, West Oakland Park, Coral Springs, Tamarac, Coconut Creek, Town of Surfside, Cutler Bay, Kendall, Kendale Lakes, The Hammocks, Aventura, Bal Harbour, Bay Harbor Islands, Key Byscayne, Biscayne Park, El Portal, Golden Beach, Indian Creek, Medley, North Bay Village, Palmetto Bay, Pinecrest, Sunny Isles Beach, Sweetwater, Cooper City, Davie, Deerfield Beach, Hillsboro Beach, Lighthouse Point, Margate, Parkland, Plantation, Sea Ranch Lakes, Southwest Ranches, Sunrise, West Park, Wilton Manors, Brownville, Calusa Club, Coral Terrace, Country Club, Allapattah, Coconut Grove, Liberty City, Little Havana, Wynwood, Country Walk, Fisher Island, Fontainebleau, Gladeview, Glenvar Heights, Golden Glades, Goulds, Ives Estates, Leisure City, Naranja, Ojus, Olympia Heights, Little Haiti, Design District, Palm Springs North, Palmetto Estates, Pinewood, Princeton, Richmond Heights, Richmond West, Sunset, Tamiami, The Crossings, Home Services Three Lakes, University Park, West Little River, Perrine.

Thermal Inspection is a requirement, under Section 8-11 (f) of the Miami Dade County Code, for buildings that have been in existence for 40 years, and every 10 years thereafter.

Miami Thermography Testing.

For an electrical system operating at 400 amperes or greater, a thermographic inspection with a written report of the following electrical equipment must be provided as applicable or as otherwise indicated below:

busways, switchgear, panelboards (except in dwelling unit load centers), disconnects, VFDS, starters, control panels, timers, meter centers, gutters, junction boxes, automatic/manual transfer switches, exhaust fans and transformers.

Thermal Imaging Inspection Report for Building Recertification.

  • Level II or III Certificate.

  • Notarized Letter stating that we are Certified Level II or III Thermographer meeting the experience required, as per the current 2021 MINIMUM INSPECTION PROCEDURAL GUIDELINES FOR BUILDING ELECTRICAL RECERTIFICATION, revised and approved by the Board of Rules and Appeals (BORA)on November 18, 2021.

  • Statement that we have inspected all required equipment, as per the current Board of Rules and Appeals (BORA) Approved – Revised November 18, 2021 MINIMUM INSPECTION PROCEDURAL GUIDELINES FOR BUILDING ELECTRICAL RECERTIFICATION (if all required equipment was inspected)

  • Summary List of all equipment inspected properly identified: labels, nameplate data, location, measurement date and local time, issues, etc.

  • Summary List of equipment not inspected and why: e.g. cover cannot be opened, safety issue, needing approval from utility company, etc.).

  • Camera information (e.g. manufacturer, specifications: resolution, accuracy, calibration, etc.).

  • Environmental information affecting Infrared Thermography Inspection (e.g. ambient temperature, wind speed, background, etc.).

  • Performance or operating information (e.g. loads, phases, voltage, type of service: one phase, three phases, delta, wye, etc.).

  • Thermal scale in each thermal photo to read temperature.

  • Use of an specific palette in the entire report unless a different one was needed to be used to identify an issue.

  • Thermal photos accompanied by visual photos of equipment with and without covers.

  • Measurement determinations.

  • Possible cause, level of the issue and prioritization (e.g. overload, contact, unbalance, open circuit, repair immediately, next programmed maintenance, etc.).

  • Any Code violation observed (e.g. improper color for cables, double tap, improper fuse, improper breaker, improper wiring, etc.).

  • Any anomaly observed (e.g. change of color, visible damage, corrosion, etc.).

  • Scan of the grounding or bonding conductors in the building main loads/meters center.

  • Any other information required to meet the standards of electrical thermographic testing inspections.

The Infrared Electrical Inspection Report will be digitally signed. PDF report will be electronically submitted to the Client. That will be the report to be submitted to the City if electronic submission os accepted, otherwise, a signed hard copy with colored photos will be provided.